Specifications of our Air Handling Units:
- Built-in speed control Knob or 0 – 10v dc control input
- Efficient EC motor (230v 1ph 50 Hz supply)
- Anodised pentapost frame with lightweight aluzinc double skin panels
- Low profile top or bottom access design
- Duties from 500 to 2500 m3/hr against 250 Pa external pressure
- Long life M5 bag filters with Diff. pressure switch (Optional F7 bag at extra cost)
- Hot water heater battery (cu/al) optimised for modern water temps
- Electric heaters include pulse control, local or remote 0 – 10v dc input
- Flexible connections fitted as std. with 30mm mez flanges
- Optional shut off damper with open/close motor fitted
Dimensions:
|
O/A Height |
O/A Width |
O/A Length |
Kg |
Bag Filter |
SL6-22 |
360mm |
660mm |
1560mm + 150 flex |
65 |
600 x 300 |
SL8-31 |
360mm |
810mm |
1560mm + 150 flex |
90 |
750 x 300 |
*Silencers 900 & 1200mm Long with 30mm flanges
Maximum Performance:
|
RPM |
m3/hr |
Input W |
Heater |
l/min |
SL6 – 22 |
3220 |
1000 |
230 |
8kW |
5.8 |
SL8-31 |
2600 |
2200 |
450 |
18kW |
12.9 |
Sound Data:
dBW re 10-12W |
|
63 |
125 |
250 |
500 |
1k |
2k |
4k |
8k |
dBA@3m |
SL6-22 |
In |
64 |
59 |
69 |
62 |
59 |
54 |
52 |
48 |
|
SL6-22 |
Out |
66 |
61 |
73 |
65 |
65 |
63 |
57 |
55 |
|
SL6-22 |
Breakout |
58 |
53 |
57 |
35 |
35 |
30 |
24 |
24 |
35 |
SL8-31 |
In |
62 |
65 |
70 |
69 |
60 |
63 |
59 |
56 |
|
SL8-31 |
Out |
65 |
68 |
73 |
72 |
69 |
66 |
62 |
59 |
|
SL8-31 |
Breakout |
57 |
60 |
57 |
42 |
39 |
33 |
29 |
26 |
40 |
Performance:
Performance with
10v DC input |
50Pa |
100Pa |
150Pa |
200Pa |
250Pa |
300Pa |
350Pa |
400Pa |
SL6-22 |
m3/hr |
1160 |
1140 |
1080 |
1030 |
960 |
920 |
850 |
780 |
|
l/s |
322 |
317 |
300 |
286 |
266 |
255 |
236 |
216 |
input W |
127 |
137 |
147 |
169 |
175 |
182 |
187 |
193 |
SL8-31 |
m3/hr |
2300 |
2230 |
2150 |
2090 |
2000 |
1900 |
1800 |
1600 |
|
l/s |
639 |
619 |
597 |
580 |
555 |
528 |
500 |
444 |
input W |
433 |
439 |
447 |
449 |
451 |
452 |
453 |
441 |